ASTM D924 Standard Test Method for Dissipation Factor (or Power Factor) and Relative Permittivity (Dielectric Constant) of Electrical Insulating Liquids

    What is ASTM D924?

    ASTM D924 is a standard test method for testing new electrical insulating liquids, as well as liquids in service or after service in cables, transformers, oil circuit breakers, and other electrical apparatus. The method provides a procedure for making referee tests at a commercial frequency of between 45 Hz and 65 Hz. The dissipation factor (or power factor) measures losses in the electrical insulating liquid in an alternating electric field, and the energy dissipated as heat. A low dissipation factor means low AC dielectric loss. The liquid’s ability to store electrical energy in an electric field is known as relative permittivity (dielectric constant). 

    Read more

    Get Certified ASTM D924 Testing for Reliable Insulating Liquid Assessment

    The performance and reliability of electrical insulating liquids are related to the dissipation factor and relative permittivity. ASTM D924 certification provides a quality control test for insulating liquids used in electrical apparatus. Qualified laboratory testing provides accurate, repeatable data for quality control, condition monitoring, and contamination/deterioration. This testing supports maintenance decisions and helps ensure reliable operation of transformers, cables, and circuit breakers. 

    What is the Scope of ASTM D924?

    ASTM D924 is a standard that covers determining the dissipation factor (or power factor) and relative permittivity (dielectric constant) of electrical insulating liquids. The standard is applicable to new liquids and liquids that are already in service or after service in cables, transformers, oil circuit breakers, and other types of electrical apparatus. Labs conduct referee tests at a commercial frequency of 45Hz to 65Hz and allow modifications acceptable for routine determinations with less accuracy.

    Read more

     The scope of ASTM D924 includes:

    • Material type: This is for electrical insulating liquids (mineral insulating oil, silicone liquids, or other liquid dielectrics used in electrical apparatus).
    • Purpose: ASTM D924 determines the dielectric loss characteristics and permittivity of insulating liquids to evaluate their quality and condition.
    • Property measured: Dissipation factor/power factor, relative permittivity/dielectric constant.
    • Method: This test determines the loss characteristics and permittivity at commercial frequencies with an appropriate test cell and measuring equipment (ASTM D924). 
    • Result: The testing laboratory obtains dissipation factor and relative permittivity values from the liquid samples it tests.
    • Test Limitations: Reference procedures at 45 Hz to 65 Hz. Some changes are allowed for standard determinations that do not need high accuracy.
    • Environmental conditions: Test conditions comprise controlled laboratory conditions for accurate measurements of the dielectric. 
    • Applications: ASTM D924 is used for quality control of new insulating liquids, condition monitoring of in-service liquids, and to assess changes due to contamination or deterioration. 

    What are the Uses of ASTM D924 Testing?

    ASTM D924 testing provides reliable dielectric property data to assess an insulating liquid’s quality. Manufacturers and engineers use these results for quality control, condition monitoring, and maintenance decisions.

    This standard-

    • New electrical insulating liquids quality control
    • In-service insulating liquids: condition monitoring of in-service insulating liquids
    • Locating faults in transformers, cables and circuit breakers
    • Assessing  the effectiveness of liquid treatment processes
    • Supporting working practices for maintenance/replacement of electrical apparatus
    • Providing data for dielectric loss assessment and permittivity measurement 

    Which materials can be tested under ASTM D924?

    ASTM D924 covers the following electrical insulating liquids: mineral insulating oils, Silicone liquids, and other liquid dielectrics. It applies to new liquids and liquids used in cables, transformers, oil circuit breakers, and other electrical apparatus.

    Why is ASTM D924 Important?

    ASTM D924 is the standard test for the dissipation factor and relative permittivity of electrical insulating liquids. Dissipation factor measures dielectric loss and serves as a quality-control indicator that may signal deterioration, processing issues, or contamination. Relative permittivity influences the electrical properties of an insulation system or a capacitor dielectric. This standard enables accurate condition assessment, supports maintenance decisions, and helps ensure reliable operation of electrical apparatus.

    ASTM D924 Equipment and Sample Preparation Guide

    ASTM D924 specifies a suitable test cell, measuring equipment, and temperature control for correct dielectric measurements. The laboratory follows standard sampling and sample preparation procedures. 

    Read more

    Sample and Specimen DetailsTechnicians collect representative samples of electrical insulating liquids according to Practices D923 for controlled dielectric testing. 
    Specimen PreparationTechnicians prepare the specimen by cleaning and filling the test cell, avoiding contamination that affects results  
    Specimen DimensionsTechnicians select sample volume based on the test cell requirements; test cells typically require 40 mL to 100 mL of liquid sample depending on cell design and electrode configuration. 
    InstrumentationThe test uses a suitable test cell, measuring equipment for dissipation factor and permittivity, a temperature control system, and calibration standards per Practice D2865. 

    Testing Procedures and Requirements for ASTM D924

    ASTM D924 is a standard test method that utilizes a test cell and measuring equipment to measure dissipation factor and the relative permittivity at commercial frequencies. This test is based on the SI units. The process is as follows:

    Read more

    Sample Preparation Technicians collect samples according to Practices D923 and prepare the test cell, avoiding contamination  
    Cell Filling Technicians fill the cleaned test cell with the liquid sample, ensuring no air bubbles or contaminants are introduced. 
    Temperature Stabilization Technicians allow the sample to reach the specified test temperature for accurate measurement. 
    Measurement Technicians measure dissipation factor and relative permittivity using suitable equipment at the specified frequency  
    Data Recording The system records dissipation factor and permittivity values for quality assessment. 

    ASTM D924 Testing Process and Data Collection

    Testing follows Practice D923 and involves taking a representative sample of the insulating liquid. Technicians clean and fill the test cell, ensuring no contamination affects the data. The sample is brought to the required test temperature, and the technicians take measurements at a commercial frequency range of 45Hz to 65Hz. The measuring equipment measures the dissipation factor and relative permittivity of the liquid. The data acquisition system is used to record the values and the laboratory report results for quality control or condition assessment. 

    Common Challenges and Troubleshooting in ASTM D924

    Due to the complexity of ASTM D924, the handling of test samples and preparation of the test cell are critical to obtaining accurate results. Contamination from the cell or sample affects measurements. The method includes all the steps necessary to clean and fill the test cell, particularly in the context of avoiding contamination. Accurate measurements of the dielectric properties require temperature control. Laboratories obtain consistent data if they prepare samples carefully, use calibrated equipment, as per practice D2865, and have standardized test conditions and trained technicians working under standardized procedures. 

    ASTM D924 Analysis Results and Interpretation

    ASTM D924 yields measurement results in SI units. It measures parameters such as dissipation factor and relative permittivity in electrical insulating liquids.

    Read more

    • Test results report dissipation factor or power factor as a decimal value or percentage (%) to indicate the dielectric loss characteristics of the insulating liquid.
    • Analysts report relative permittivity, also called dielectric constant, as a dimensionless value that characterizes the liquid’s ability to store electrical energy.
    • The laboratory interprets lower dissipation factor values as lower dielectric losses under the specified test conditions, while considering the applicable insulating-liquid requirements.
    • Analysts compare dissipation factor and relative permittivity with baseline or previous measurements to identify changes that may indicate contamination, degradation, or processing effects.
    • Engineers compare the measured dielectric properties with applicable specifications for the insulating liquid and use the results to support quality-control and condition-monitoring decisions for electrical apparatus.

    Link to ASTM D924

    FAQ

    What materials can be tested under ASTM D924?
    ASTM D924 covers electrical insulating liquids, such as insulating oils for use in mineral oils and silicone liquids, and other liquid dielectrics for electrical apparatus.
    ASTM D924 specifies that a test cell and a temperature control system are required, along with the equipment necessary to measure dissipation factor and permittivity, and calibration standards according to Practice D2865.
    ASTM D924 provides a procedure for making referee tests at a commercial frequency between 45 Hz and 65 Hz.
    Dissipation factor is a measure of the losses in the electrical insulating liquids. A good dissipation factor means low AC dielectric losses. Measurement is used to monitor quality and as a clue to changes in quality caused by contamination, deterioration, or processing.

    Updated on October 7, 2026

    Malhar Khole
    About Author
    Malhar Khole is a Material Testing Associate at Matestlab Inc. and holds a postgraduate degree in Material Science and Technology from IIT (BHU), Varanasi.
    Know More
    Testimonials
    Real results
    Engineers trust us with what matters most
    Why Choose Matestlab?
    Matestlab is a unified testing services partner based in the USA. Matestlab offers raw material and product testing services through accredited, expert laboratories primarily based in the USA. Matestlab supports physical, thermal, chemical, electrical, mechanical, environmental, and characterization testing needs through its global network of 2200+ accredited testing laboratories. Matestlab's in-house materials science experts curate and design comprehensive testing programs matched to the sample material and specific testing need, with regulatory requirements and confidentiality in mind.

    If you are looking for a managed and trusted testing partner to achieve your research goals, feel free to schedule a meeting with us or send us a request at connect@matestlabs.com to learn more about our services. For a quick quote, call us at (302)244-7710. We are happy to serve you.
    Start Your Testing
    Project Today
    Define your requirements and get access to
    specialized laboratories ready to deliver results
    Partners with us
    Clients
    Vendors
    Process for testing
    • STEP 01

      You share your testing requirements

    • STEP 02

      You share your sample(s)

    • STEP 03

      We deliver your test reports

    Get your testing done

    Let us know your testing requirements and we will be right back with a solution.

      Let us root for each other. Collaborate to grow, expand, and accelerate our businesses.

      Partner with us