ASTM E119 specifies the boundary of coverage around assemblies of masonry units and composite structural assemblies for buildings: load-bearing and non-load-bearing walls and partitions, columns, girders, beams, slabs, and composite slab and beam assemblies for floors and roofs. The coverage is for the specified furnace fire exposure, with a standard time-temperature curve, coupled with exposure by a hose stream for wall assemblies exposed to the test defined by Practice E2226. The exposure does not represent absolute fire-test response of equivalent assemblies, but rather is based on a relative comparison of fire-test response between assemblies, as there is a broad range of fire-loaded assemblies, different ventilation, and assembly configurations outside of the test.
The scope of ASTM E119 includes:
- Material type: Load-bearing and non-load-bearing walls, partitions, columns, girders, beams, slabs, and composite slab and beam assemblies.
- Purpose: Determination of the duration a building assembly contains a fire, retains structural integrity, or both.
- Property evaluation: Fire containment, structural integrity, and unexposed-surface temperature rise during furnace exposure.
- Testing method: A furnace exposes the assembly to a standard time-temperature curve, and thermocouples track unexposed-surface temperature rise.
- Results: A time-based fire resistance rating, such as one hour or two hours, based on the assembly’s performance.
- Test limitation: Furnace exposure provides a relative measure of fire-test response rather than a prediction of every real-world fire condition.
- Use conditions: Wall assemblies undergo a standard fire hose stream exposure after the furnace phase, applied under Practice E2226.
- Application: Supports fire-rated egress paths, stairwells, elevator shafts, and mechanical room classifications in building codes.
What are the Uses of ASTM E119 Testing?
ASTM E119 testing allows manufacturers and designers to provide a verifiable fire resistance rating for a wall, floor, column, or beam assembly. Codes refer to these ratings to classify an assembly as an egress or life-safety feature. This standard-
- Assigns time-based fire resistance ratings such as one hour or two hours to building assemblies.
- Supports code compliance for fire-rated walls, floors, columns, and beams.
- Compares fire-test response across different assembly designs and materials.
- Verifies structural integrity under combined thermal and hose stream exposure.
- Assists manufacturers in developing and certifying fire-rated building products.
- Supports classification of egress paths, stairwells, and mechanical rooms in building codes.
Which materials can be tested under ASTM E119?
ASTM E119 applies to assemblies of masonry units and composite structural materials, including load-bearing and non-load-bearing walls and partitions, columns, girders, beams, slabs, and composite slab and beam assemblies for floors and roofs. The specimens of load-bearing walls and partitions shall have an area of at least 100 sq.ft. of exposed surface, no one of which shall be less than 9 ft. in either direction. The specimens of beams, for floors and roofs, shall have a width not exceeding 7 ft., measured from the center of the beam.
Why is ASTM E119 Important?
Fire resistance ratings are used to define life-safety requirements of building code related to exit access, stairwells, and fire barriers. Testing an assembly under different conditions may result in an assembly having a fire-test response that does not reflect its rating. Fire resistance ratings keep a standard for different manufacturers, laboratories, and jurisdictions based on the standards of ASTM E119, allowing for life-safety decisions to be made based on accurate information specific to jurisdiction and building type.